A 3-D Finite-Element Method Approach for Analyzing Different Short Circuit Types in a Saturated Iron Core Fault Current Limiter.

التفاصيل البيبلوغرافية
العنوان: A 3-D Finite-Element Method Approach for Analyzing Different Short Circuit Types in a Saturated Iron Core Fault Current Limiter.
المؤلفون: Santos, Gabriel dos, Martins, Flavio Goulart R., Sass, Felipe, Sotelo, Guilherme Goncalves, Morandi, Antonio, Grilli, Francesco
المصدر: IEEE Transactions on Applied Superconductivity; Sep2022, Vol. 32 Issue 6, p1-13, 13p
مصطلحات موضوعية: FAULT current limiters, SUPERCONDUCTING fault current limiters, SHORT circuits, FINITE element method, MAGNETIC flux density, SUPERCONDUCTING coils, IRON-based superconductors, ELECTRIC power systems
مستخلص: In several cases, substations have become incapable of supporting faults due to increase in short-circuit levels. Fault current limiters (FCLs) are a potential solution for this problem. Among several FCL topologies presented in the literature, the saturated iron core superconducting fault current limiter (SIC-SFCL) has shown promising results in real tests in substations. In this context, this article presents the impacts of different kinds of short circuit on the SIC-SFCL device. To reproduce various types of fault, the SIC-SFCL is modeled in a 3-D framework considering both ferromagnetic and superconducting nonlinearities. Moreover, the proposed 3-D finite-element method model can couple the SIC-SFCL to the electric power system, also representing the electrical grid and the protection systems. For this investigation, the dc-bias superconducting coil’s normalized current density and the iron cores’ magnetic flux density are examined in light of different kinds of short circuit. The simulations are compared with measurements in a bench prototype, showing a maximum error of 16.5%. Furthermore, different types of short circuit are investigated and compared, which is possible only using a 3-D model. The highest limitation occurs in the phase-to-phase short-circuit case. In the dc circuit of the SIC-SFCL, the highest transient period happens in the single-phase short circuit. Finally, the phase-to-phase fault presents the highest dc current during the transient. [ABSTRACT FROM AUTHOR]
Copyright of IEEE Transactions on Applied Superconductivity is the property of IEEE and its content may not be copied or emailed to multiple sites or posted to a listserv without the copyright holder's express written permission. However, users may print, download, or email articles for individual use. This abstract may be abridged. No warranty is given about the accuracy of the copy. Users should refer to the original published version of the material for the full abstract. (Copyright applies to all Abstracts.)