دورية أكاديمية

Feasibility of condensate water recycle of split air handling unit in Chinese University buildings.

التفاصيل البيبلوغرافية
العنوان: Feasibility of condensate water recycle of split air handling unit in Chinese University buildings.
المؤلفون: Xiang Deng, Yiyun Shen, Senwang Yang, Jingyang Feng, Si Wang, Dongyue Li, Yanru Li
المصدر: Energy & Built Environment; Apr2024, Vol. 5 Issue 2, p309-315, 7p
مصطلحات موضوعية: COLLEGE buildings, DEW point, CAPITAL cities, HOT weather conditions, REGRESSION analysis
مصطلحات جغرافية: CHINA
مستخلص: Recycling the condensate water of the air conditioner could be explored as an alternative water source to contribute to building the green campus. This paper explored the condensate water production through actual measurement based on a split air handling unit (SAHU) in a university building. Then, the statistical analysis was used to analyze the recycling feasibility and the impact factors of the condensate water production in 31 Chinese provincial capital cities to obtain the recycling potential map of the condensate water generated from a SAHU. Results showed that: (1) In the measurement, the amount of condensate water produced by a single split air conditioner was 1.6 kg from 12:40 to 13:40. Therefore, the daily output of condensate water of the air conditioner with the university operation schedule could reach 52.99 kg during the main air-conditioning season. (2) Among the 31 provincial capital cities in China, the largest condensate water outputs could be found in the Hot Summer and Warm Winter zone and the Hot Summer and Cold Winter zone, with an average monthly output of 1600 kg and 1100 kg, respectively. (3) Regression analysis showed that the dry-bulb temperature and dew point temperature of outdoor air had the highest positive and significant influence on condensate water production. The objective of this study is to provide theoretical guidance for the design and energy conservation evaluation of the feasibility of SAHU condensate water recycling in universities. [ABSTRACT FROM AUTHOR]
Copyright of Energy & Built Environment is the property of KeAi Communications Co. and its content may not be copied or emailed to multiple sites or posted to a listserv without the copyright holder's express written permission. However, users may print, download, or email articles for individual use. This abstract may be abridged. No warranty is given about the accuracy of the copy. Users should refer to the original published version of the material for the full abstract. (Copyright applies to all Abstracts.)
قاعدة البيانات: Complementary Index
الوصف
تدمد:26661233
DOI:10.1016/j.enbenv.2022.10.006