Feasibility Analysis of the Operation Strategies for Combined Cooling, Heating and Power Systems (CCHP) based on the Energy-Matching Regime

التفاصيل البيبلوغرافية
العنوان: Feasibility Analysis of the Operation Strategies for Combined Cooling, Heating and Power Systems (CCHP) based on the Energy-Matching Regime
المؤلفون: Junrong Mo, Lin Shi, Xiaoye Dai, Lejun Feng
المصدر: Journal of Thermal Science. 29:1149-1164
بيانات النشر: Springer Science and Business Media LLC, 2020.
سنة النشر: 2020
مصطلحات موضوعية: Quantification methods, Electrical load, Computer science, 020209 energy, 02 engineering and technology, Thermal load, Condensed Matter Physics, Energy matching, Reliability engineering, Power (physics), Nameplate capacity, Electric power system, 020303 mechanical engineering & transports, 0203 mechanical engineering, 0202 electrical engineering, electronic engineering, information engineering, Energy (signal processing)
الوصف: Although numerous studies have considered the two traditional operation strategies: following the electric load (FEL) and following the thermal load (FTL), for combined cooling, heating, and power (CCHP) systems in different case studies, there are limited theoretical studies on the quantification methods to assess the feasibility of these two strategies in different load demands scenarios. Therefore, instead of a case study, we have undertaken a theoretical analysis of the suitable application scenarios for FEL and FTL strategies based on the energy-matching performance between systems’ provision and users’ demands. To compare the calculation models of energy saving rate (ESR) for FEL and FTL strategies in the left and right sub-regions of the energy-supply curve, a comprehensive parameter (χ) that combines three inherently influential factors (off-design operation parameter, energy-matching parameter, and install capacity coefficient) is defined to determine the optimal installed capacity and feasibility of FEL or FTL strategies quantitatively. The results indicate that greater value of χ will contribute to a better energy saving performance, and FEL strategy shows better performance than FTL in most load demands scenarios, and the optimal installed capacity occurs when the load demand points were located in different regions of the energy-supply curve. Finally, taking a hotel in Beijing as an example, the value of the optimal install capacity coefficient is 0.845 and the FEL strategy is also suggested, and compared to the maximum install capacity, the average values of the ESR on a typical summer day, transition season, and winter can be enhanced by 3.9%, 8.8%, and 1.89%, respectively.
تدمد: 1993-033X
1003-2169
URL الوصول: https://explore.openaire.eu/search/publication?articleId=doi_________::7d1292aa267fffe038c0927dd65e435a
https://doi.org/10.1007/s11630-020-1314-2