Testing and demonstration of model predictive control applied to a radiant slab cooling system in a building test facility

التفاصيل البيبلوغرافية
العنوان: Testing and demonstration of model predictive control applied to a radiant slab cooling system in a building test facility
المؤلفون: Philip Haves, Carlos Duarte, Xiufeng Pang, Frank Chuang
المصدر: Energy and Buildings. 172:432-441
بيانات النشر: Elsevier BV, 2018.
سنة النشر: 2018
مصطلحات موضوعية: Computer science, Heuristic (computer science), 020209 energy, FLEXLAB, Radiant slab systems, 02 engineering and technology, Toolchain, Automotive engineering, Engineering, Affordable and Clean Energy, Chilled water, 0202 electrical engineering, electronic engineering, information engineering, Water cooling, Model predictive control, Electrical and Electronic Engineering, Civil and Structural Engineering, Building & Construction, Experimental study, business.industry, Mechanical Engineering, Building and Construction, Energy consumption, Energy performance, Built Environment and Design, Slab, business, Thermal energy
الوصف: Radiant slab systems have the potential to significantly reduce energy consumption in buildings. However, control of radiant slab systems is challenging. Classical feedback control is inadequate due to the large thermal inertia of the systems and heuristic feed-forward control often leads to unacceptable indoor comfort and may not achieve the full energy savings potential. Model predictive control (MPC) is now attracting increasing interest in the building industry and holds promise for radiant systems. However, an often-cited barrier to its implementation in the building industry is the high computational cost and complexity relative to the feedback controls used in conventional systems. The objectives of this study were to (i) verify the correct operation of an open source MPC toolchain developed for radiant slab systems, and (ii) demonstrate its efficacy in a test facility. A matched pair of cells in the FLEXLAB building test facility at the Lawrence Berkeley National Laboratory was used in the study. The proposed MPC toolchain was implemented in one cell and the performance compared to that of the other cell, which used a conventional heuristic control strategy. The results showed that the simplified MPC approach applied in the toolchain worked as expected and realized energy savings over the conventional control strategy. The MPC yielded 42% chilled water pump power reduction and 16% cooling thermal energy savings, while maintaining equal or better indoor comfort.
وصف الملف: application/pdf
تدمد: 0378-7788
URL الوصول: https://explore.openaire.eu/search/publication?articleId=doi_dedup___::fdade7b693f72f170734e696741a5658
https://doi.org/10.1016/j.enbuild.2018.05.013
حقوق: OPEN
رقم الأكسشن: edsair.doi.dedup.....fdade7b693f72f170734e696741a5658
قاعدة البيانات: OpenAIRE