Experimental study on the operating performance of the air source heat pump (ASHP) with variable outdoor airflow rate under the standard frosting condition

التفاصيل البيبلوغرافية
العنوان: Experimental study on the operating performance of the air source heat pump (ASHP) with variable outdoor airflow rate under the standard frosting condition
المؤلفون: Shimin Liang, Han Wang, Xuefeng Gao, Xiaohui Tian, Hui Zhu, Songtao Hu, Chunwen Lin
المصدر: Energy and Built Environment, Vol 5, Iss 5, Pp 719-726 (2024)
بيانات النشر: KeAi Communications Co., Ltd., 2024.
سنة النشر: 2024
المجموعة: LCC:Environmental technology. Sanitary engineering
LCC:Building construction
مصطلحات موضوعية: ASHP, Variable outdoor airflow rate, Frosting, Heating performance, Environmental technology. Sanitary engineering, TD1-1066, Building construction, TH1-9745
الوصف: Frosting is a common phenomenon of the ASHP under the heating mode in winter, and the outdoor air flow rate flowing through the evaporator of the ASHP was always thought to be a major contributor. In order to validate its contribution, effects of outdoor fan airflow rate on the performance of air source heat pumps (ASHPs) were investigated under the winter heating condition. The experiment was conducted in a laboratory at the standard 2 °C air dry bulb temperature (DB)/ 1 °C air wet bulb temperature (WB) frosting condition, which enabled the analysis of the operating performance, frosting performance, and heating performance of the ASHP unit by changing the airflow rate of the outdoor fan. Results showed that as the airflow rate of the outdoor fan reduced from 100% to 36%, the operating performance decline and the elevated frosting-defrosting loss were observed. Meanwhile, both the frosting rate and the operating efficiency during frosting-defrosting cycles showed an increasing trend then followed by decreasing tendency. The maximum frosting rate and operating efficiency were 0.92 g/m2.min and 2.92, respectively, which were observed at 74% airflow rate of the outdoor fan of the ASHP unit. The observation implied the existence of the “minimum frosting suppression airflow rate”. At 36% airflow rate of the outdoor fan of the ASHP unit, however, the performance of the ASHP unit was attenuated greatly, with the frosting-defrosting efficiency loss coefficient of 0.47, the heating capacity and COP reduction by 51.5 and 38.8%, respectively. These findings provided significant references to the optimization of ASHPs performance with variable airflow rate of the outdoor fan under frosting conditions.
نوع الوثيقة: article
وصف الملف: electronic resource
اللغة: English
تدمد: 2666-1233
Relation: http://www.sciencedirect.com/science/article/pii/S266612332300048X; https://doaj.org/toc/2666-1233
DOI: 10.1016/j.enbenv.2023.06.001
URL الوصول: https://doaj.org/article/bf2c4670be5e4a90a2e386c7d7bebd1e
رقم الأكسشن: edsdoj.bf2c4670be5e4a90a2e386c7d7bebd1e
قاعدة البيانات: Directory of Open Access Journals
الوصف
تدمد:26661233
DOI:10.1016/j.enbenv.2023.06.001